Mns-Up Ups General Characteristics - ABB MNS-Up Service Manual

Hide thumbs Also See for MNS-Up:
Table of Contents

Advertisement

14
M N S - U P S E R V I C E M A N U A L
3.1

MNS-Up UPS general characteristics

General characteristics
General characteristics - Frame
Model: MNS-Up
Power ratings:
Apparent power per section
Apparent active power per section
Power, range
UPS type: on-line, transformer-free, modular,
decentralized parallel
architecture
Parallel capability: up to 6 MNS-Up sections
Battery: not included
Performance classification: VFI-SS-111
Mechanical
Dimensions (width × height × depth)
Mass, approx. per MNS-Up section
(500kW system, with / without 5 modules)
Acoustic noise at 1 m
- in normal mode (at <=25°C) at 100% load
- in normal mode (at <=25°C) at 50% load
Safety
IEC 62040-1
Access: operator/restricted
Electromagnetic compatibility
IEC 62040-2
compliant
Emission UPS Cat/Immunity UPS Cat
Environmental
Storage temperature range
Ambient temperature
Relative humidity range (non-condensing)
Max. altitude without de-rating
Values
500
500
100 - 3000
1400 x 2200 x 1400 or
1400 x 2200 x 1600
1450 / 950
84,9
av. at later stage
C3
- 25 - + 70
0 - + 40
≤ 95
1000
Unit
kVA
kW
kW
mm
mm
kg
dBA
dBA
°C
°C
%
m