G E N E R A L T E C H N I C A L D ATA

General technical data

3
General technical data
Enclosed low-voltage switchgear
and controlgear assemblies
Seismic
Standards
Vibration
Shock
Protection against electric shock Common aspects for installation and equipment
Test certificates
Rated voltages
Electrical data
Rated currents
Arc fault containment
Dimensions
Surface protection
Degree of protection
Mechanical
characteristics
Separation Form
External mechanical impact (IK)
Plastic components
Steel components
Forms of separation
Internal subdivision
Paint finish
Extras
Busbar system
Optional
General rules
Power switchgear and controlgear assemblies
Testing under conditions of arcing due to
internal fault (internal arc)
Recommended practices for nuclear generating
station
Environmental testing Test Fc: Vibration
(sinusoidal)
Environmental testing
Test Ea and guidance: Shock
General rules
ASTA / United Kingdom, DEKRA / Netherlands, Germanischer Lloyd, Hamburg / Germany
IPH, Institut für Prüffeld- und Hochspannungstechnik, Berlin / Germany
High Power Laboratory, ABB AG, Ratingen / Germany
Technology center laboratory, ABB s.r.o, Brno / Czech Republic
Rated insulation voltage U
i
Rated operating voltage U
e
Rated impulse withstand voltage U
Overvoltage category
Degree of pollution
Rated frequency
Main busbar
Rated current I
e
Rated peak withstand current I
pk
Rated short-time withstand current I
Distribution bars
Rated current I
e
Rated peak withstand current I
pk
Rated short-time withstand current I
Rated operational voltage
Prospective short-circuit current
Duration
Criteria (IEC TR 61641)
Sections and frames
Recommended height
Recommended width
Recommended depth
Basic grid size
Frame incl. Internal subdivision
Cladding, internal, roof and bottom plate
Cladding, external, front, rear and side
According to IEC 61439
Halogen-free, self-extinguishing,
flame retardant, CFC-free
Frame incl. internal subdivisions 2,0 / 2,5 mm
Cladding, internal 1,5 / 2,0 mm; external 1,5 mm
up to form 4
up to form 3 UPS sections
Equipment compartment
Busbar compartment
Cable compartment
Enclosure
Busbars
Project specific solutions available on request
6 / 8 / 12 kV, depending on equipment
imp
cw
cw
400, 600, 800, 1 000, 1 200, 1 400 mm
400, 600, 800, 1 000, 1 200, 1 400, 1 600 mm
powder coated RAL 7035 (light grey)
External for UPS sections IP20
IEC 60707, DIN VDE 0304 part 3
Special colours (standard RAL 7035, other
Bare copper Insulated with heat shrinkable
sleeving Silver or tin plating Aluminium
13
IEC 61439 - 1
IEC 61439 - 2
IEC TR 61641
IEC 60980
IEC 60068-2-6
IEC 60068-2-27
IEC 61140
IEC 61439-1
1 000 V 3~, 1 500 V-
690 V 3~, 750 V-
II / III / IV
3
up to 60 Hz
up to 6 300 A
up to 220 kA
up to 100 kA
up to 2 000 A
up to 220 kA
up to 100 kA
up to 690 V
up to 100 kA
300/500 ms
1 to 7
ISO 2768
2 200 mm
*)
E = 25 mm acc. to DIN 43660
Zinc or Alu-zinc coated
Zinc or Alu-zinc coated
Zinc or Alu-zinc coated and
External from IP 30 to IP 54
Internal from IP XXB
up to form 4
up to form 3 UPS sections
up to IK10
colours on request)
busbar systems