Permitted Cables For The Data Communication Area; Cross Section Of The Ac Cable - Fronius Primo GEN24 3.0 Plus Operating Instructions Manual

Grid-connected inverter
Hide thumbs Also See for Primo GEN24 3.0 Plus:
Table of Contents

Advertisement

Permitted cables
Cables with the following design can be connected to the terminals of the inverter:
for the data com-
munication area
IMPORTANT!
Connect the individual conductors to an appropriate ferrule if several individual conduct-
ors are connected to one input of the push-in terminals.
WSD connections with push-in terminal
Dis-
Stripping
tance
length
max.
100 m
10 mm
109 yd
0.39 inch
Modbus connections with push-in terminal
Dis-
Stripping
tance
length
max.
300 m
10 mm
328 yd
0.39 inch
IO connections with push-in terminal
Dis-
Stripping
tance
length
max.
30 m
10 mm
32 yd
0.39 inch
LAN connections
Fronius recommends using at least CAT 5 STP (shielded twisted pair) cables and a maximum distance of
100 m (109 yd).
Cross section of
For a standard M32 metric screw joint with a reducer:
the AC cable
Cable diameter from 7-15 mm
When using an M32 metric screw joint (reducer removed):
cable diameter from 11-21 mm
(with a cable diameter of less than 11 mm, the strain-relief force is reduced from 100 N to
a maximum of 80 N)
-
Copper: round, solid
-
Copper: round, fine-stranded
Fine-stran-
Solid
ded
2
0.14-1.5 mm
0.14-1.5 mm
AWG 26-16
AWG 26-16
Fine-stran-
Solid
ded
2
0.14-1.5 mm
0.14-1.5 mm
AWG 26-16
AWG 26-16
Fine-stran-
Solid
ded
2
0.14-1.5 mm
0.14-1.5 mm
AWG 26-16
AWG 26-16
Fine-stran-
Fine-stran-
ded with fer-
ded with fer-
rules with
rules without
collar
2
2
0.14-1 mm
0.14-1.5 mm
AWG 26-18
AWG 26-16
Fine-stran-
Fine-stran-
ded with fer-
ded with fer-
rules with
rules without
collar
2
2
0.14-1 mm
0.14-1.5 mm
AWG 26-18
AWG 26-16
Fine-stran-
Fine-stran-
ded with fer-
ded with fer-
rules with
rules without
collar
2
2
0.14-1 mm
0.14-1.5 mm
AWG 26-18
AWG 26-16
Cable recom-
mendation
collar
min. CAT 5
2
UTP (unshiel-
ded twisted
pair)
Cable recom-
mendation
collar
min. CAT 5
2
STP (shielded
twisted pair)
Cable recom-
mendation
collar
Single con-
2
ductor pos-
sible
55