Fronius Primo GEN24 3.0 Plus Operating Instructions Manual page 125

Grid-connected inverter
Hide thumbs Also See for Primo GEN24 3.0 Plus:
Table of Contents

Advertisement

7
8
9
Insert the PC board into the inverter and
secure with the four screws (TX20) sup-
plied at a torque of 1.0 ‑ 1.2 Nm.
Fasten the ground conductor with a cross
section of at least 6 mm² to the ground
electrode terminal using a screwdriver
(TX20) and a torque of 1.8 - 2 Nm.
IMPORTANT!
Depending on national standards and
guidelines, a larger cross section of the
ground conductor may be required.
The use of other inputs can make it difficult
to insert the connection area divider or
damage the ground conductor.
Strip the insulation on the single conduct-
ors by 12 mm and secure to the corres-
ponding slot of the terminal on the PC
board with a torque of 1.2 - 1.5 Nm.
IMPORTANT!
The cable cross section must be selected
according to the specifications for the
respective inverter power category (see
chapter
Permitted cables
on page 54).
125