Fronius Primo GEN24 3.0 Plus Operating Instructions Manual page 68

Grid-connected inverter
Hide thumbs Also See for Primo GEN24 3.0 Plus:
Table of Contents

Advertisement

4
5
6
68
Select the cable cross section in accord-
ance with the instructions in
cables
from page 54.
Strip the insulation of the single conduct-
ors by 12 mm. Lift to open the terminal's
operating lever and insert the stripped
single conductor into the slot provided, in
each case as far as it will go. Then close
the operating lever until it engages.
NOTE!
No multi-wire connections are possible
with this terminal type.
Only one conductor may be connected to
each pin. The DC cables can be connec-
ted to the DC terminals without ferrules.
CAUTION!
Risk due to overvoltage when using
other slots on the terminal.
This may result in damage to the battery
and/or the solar module due to discharge.
Only use the designated slots for bat-
tery connection.
CAUTION!
Danger due to polarity reversal at the
terminals.
Serious substantive damage to the PV
system may result.
Use a suitable measuring instrument
to check the polarity of the DC cabling
when the battery is switched on.
The maximum voltage for the battery
input must not be exceeded (see
Technical data
on page 137).
Permitted

Advertisement

Table of Contents
loading

Table of Contents