emmeti CTTS RF User Manual page 53

Radiofrequency digital programmable thermostat
Table of Contents

Advertisement

Available languages

Available languages

"Open window" function sensitivity - Sens (only if Fin = On)
This parameter allows to choose the intervention
sensitivity among 3 possible values:
-
(low sensitivity): corresponds to a reduction in
the measured temperature of 3°C in 6 minutes
-
(normal sensitivity): corresponds to a
reduction in the measured temperature of 1.5°C in
6 minutes. This setting is the factory default setting
-
(high sensitivity): corresponds to a reduction
in the measured temperature of 0.5°C in 6 minutes
If the "open window" function is activated too often, it is advisable to reduce the
sensitivity. On the contrary, if the function does not work when desired, increase the
sensitivity.
Duration of the "open window" function - dEl (only if Fin = On)
This parameter represents the duration of the stay in
OFF / antifreeze mode following the activation of the
"open window" function. You can choose between
15, 30 (factory value), 45, 60, 75 or 90 minutes.
Password for key lock
It's possible to set a key lock if the programmable
thermostat is installed in public places or however
if you want to prevent anyone from modifying the
operation parameters.
To set a password, enter on field
between 001 and 999. To deactivate the password
until "__ _" appears.
press the key
When the keyboard is locked, the thermostat performs all its functions using the set
regulation parameters.
If the key lock is active and one key is pressed, the display shows for a few seconds
the writing
with flashing dashes: enter the password to unlock the keyboard,
which will be locked for 30 seconds from the last pressure.
a value
CTTS RF Radiofrequency digital programmable thermostat User Manual
- 19 -