Items Not Included; Items Sold Separately - Mitsubishi Electric MCC-50A Installation And Instruction Manual

Cloud system connection device
Table of Contents

Advertisement

5-1. Items not included

The following items are required to install the MCC-50.
Items not included
Locknuts and bushing
Sleeved ring terminal
AC power cable/Protective
ground wire
Transmission cable
Relay (for external input)
Relay (for external output)
LAN cable (when connecting
to the cloud system using a
wired network)
Switching HUB (as necessary)
Broadband router (as necessary)
Fuse
Overcurrent
breaker (fuse or
Circuit breaker
circuit breaker)
*2
Earth leakage breaker
A terminal device with connection
to the Internet
*1 PE: Polyethylene, PVC: Polyvinyl chloride
*2 Use a breaker with a contact distance of 3 mm (1/8 in) or more.

5-2. Items sold separately

Items sold separately
External input/output adapter
WT09836X01
Must be suitable for the conduit tube to be used.
M3.5 ring terminal (for AC power cables (L/L1, N/L2) and M-NET transmission cables (A, B,
S))
M4 ring terminal (for protective ground wire)
Type: Sheathed cable (should not be lighter than ordinary sheathed cable IEC 60227.)
(designation 60227 IEC 53)
Recommended type: VCT, VVF, VVR, or its equivalent
Size: 0.75 to 2 mm² (ø1.0 to ø1.6 mm), AWG 18 to 14
Protective ground wire color: green/yellow
* Use a wire with an appropriate diameter so that the wire can be fixed with the cable tie below the
terminal block. A diameter of 10 mm (25/64 in) is recommended.
Type: Shielded cable
● CPEVS ø1.2 mm
● CVVS 1.25 to 2 mm²
* CPEVS: PE
* CVVS: PVC
Contact rating
Rated voltage: 12 or 24 VDC
Rated current: 10 mA or above
Minimum applied load: DC 1 mA
Operation coil
Rated voltage: 12 or 24 VDC
Power consumption: Max. 0.9 W
Category 5 or above straight cable (Max. 100 m (328 ft))
A communication speed of 100 Mbps or faster is recommended.
Rated current: 3 A
* When using a fuse, use it in combination with a switch (rated current: 3 A).
Type: Bipolar (2P2E)
Rated current: 3 A
Type: Bipolar (2P2E)
Rated current: 3 A or above
*2
Rated current sensitivity: 30 mA
Operation time: Max. 0.1 sec
PC, smartphone, tablet, etc.
Model name
PAC-YG10HA-E
Specifications
*1
insulated PVC
*1
jacketed shielded communication cable
*1
insulated PVC
*1
jacketed shielded control cable
Required when using the external input/output function
12
Remarks

Advertisement