Wiring Guidelines; Axlink Data And Power Connections; Checking Axlink Status - AMX MIO R-2 Operation/Reference Manual

Device family
Hide thumbs Also See for MIO R-2:
Table of Contents

Advertisement

Wiring Guidelines

The Mio Modero IR requires 12 VDC power to operate properly. The power is supplied by the AMX
system's AxLink cable. The maximum wiring distance between the Central Controller and the receiver is
determined by power consumption, supplied voltage, and the wire gauge used for the cable. The
following table lists wire sizes and the maximum lengths allowable between the receiver and the Central
Controller. The maximum wiring lengths are based on a minimum of 13.5 volts available at the Central
Controller's power supply.
Wiring Specifications @ 35 mA
Maximum Wiring Length
Wire Size
18 AWG
20 AWG
22 AWG
24 AWG

AxLink Data and Power Connections

The Mio Modero IR uses a four-pin mini AxLink connector for power and data.
Connect the control system's AxLink connector to the AxLink connector on the rear panel of the Mio
Modero IR for data and 12 VDC power as shown in FIG. 14.
PWR +
AXP
AXM
GND -
Mio Modero
FIG. 14
AxLink straight-thru wiring
For wire prepartaion guidelines, refer to Preparing captive wires section on page 8.

Checking AxLink Status

The AxLink LED, shown in FIG. 12, lights to indicate AxLink power/data status as follows:
• 1 blink per second
• 2 blinks per second Indicates the devices specified in the Master program do not match the devices found.
• 3 blinks per second Indicates AxLink communication error.
• Full On
If the LED is on and not flashing, disconnect the AxLink connector and recheck all AxLink connections.
Then, reconnect the AxLink connector to the panel and verify the LED is flashing once per second.
Mio Modero Device Family
Distance
3000 feet (914.40 m)
2121.64 feet (646.68 m)
1,322.75 feet (403.17 m)
833.80 feet (254.14 m)
Indicates power is active and AxLink communication is working.
Indicates the following conditions:
• There is no AxLink control or activity, but power is On.
• The Axcess program is not loaded.
Mio Modero IR
PWR +
AXP
AXM
GND -
Control System
17