Technical Specifications - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Line Modules
5.3 Active Line Modules
5.3.6

Technical specifications

Table 5- 21
Technical data for Active Line Modules, 3 AC 380 ... 480 V, Part 1
Article number
Rated power
- At I
(50Hz 400V)
L DC
- At I
(50Hz 400V)
H DC
- At I
(60Hz 460V)
L DC
- At I
(60Hz 460V)
H DC
DC-link current
- Rated current I
N DC
- Base load current I
L DC
- Rated current I
H DC
- Maximum current I
max DC 1)
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- DC-link voltage
Infeed/regenerative feedback current
- Rated current I
N E
- Maximum current I
2)
max E
Pulse frequency
Electronics current consumption (24 V DC)
Cooling method
Power loss, max.
3)
- At 50 Hz 400 V
- At 60 Hz 460 V
- Dissipated to the ambient air
Max. coolant temperature
- Without derating
- With derating
Rated flow rate
Pressure drop, typical
at the rated flow rate
4)
Liquid volume of integrated heat exchanger
DC-link capacitance
- Active Line Module
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
186
6SL3335–
7TE35–0AA3
kW
300
kW
270
HP
500
HP
400
A
549
A
535
A
489
A
823
V
3 AC 380 -10% (-15% < 1 min) ... 3 AC 480 +10%
ACrms
Hz
V
DC
V
DC
A
490
A
735
kHz
4
A
1.5
Liquid cooling with integrated heat exchanger made of
Stainless
steel
kW
3.1
kW
3.36
kW
0.14
° C
45
° C
50
l/min
12
Pa
70000
dm³
0.91
µF
9600
dB(A)
52
mm²
2 x 240
mm²
Busbar
mm²
2 x 240
7TE36–1AA3
7TE38–4AA3
380
500
335
465
600
700
500
700
677
941
661
917
603
837
1017
1410
47 ... 63Hz
24 (20.4 ... 28.8)
1.5 x U
line
605
840
907
1260
2.5
2.5
1.6
1.6
Aluminum
Aluminum
4.82
5.3
5.25
5.75
0.17
0.23
45
45
50
50
16
16
70000
70000
0.74
0.74
12600
17400
54
54
Flat connection for M12 screw
4 x 185
4 x 185
Busbar
Busbar
4 x 185
4 x 185
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
7TE41–0AA3
630
545
900
800
1100
1075
982
1654
985
1477
2.5
1.6
Aluminum
7.9
8.53
0.44
45
50
27
70000
1.56
18900
56
Busbar
Busbar
Busbar