Danger to life through electric shock due to the residual charge of the DC-link capacitors
Because of the DC-link capacitors, a hazardous voltage is present for up to five minutes
after the power supply has been switched off.
Contact with live parts can result in death or serious injury.
• Only open the device after five minutes have elapsed.
• Measure the voltage before starting work on the DCP and DCN DC-link terminals.
Danger to life due to high leakage currents caused by an interrupted external protective
conductor
The drive components conduct a high leakage current via the protective conductor.
Touching conductive parts when the protective conductor is interrupted can result in death
or serious injury.
• Ensure that the external protective conductor satisfies at least one of the following
Danger of an accident due to missing warning labels in the national language.
Missing warning labels in the national language can result in death or serious injury.
• Attach the component warning labels in the national language.
Fire hazard due to overheating because of inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel through
smoke development and fire. This can also result in increased downtime and reduced
service lives for Motor Modules.
• Observe the cooling clearances above, below, and in front of the Power Modules which
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
DANGER
WARNING
conditions:
– It has been laid so that it is protected against mechanical damage.
– For an individual core, it has a cross-section of at least 10 mm² Cu.
– If it is a conductor of a multi-conductor cable, it has a cross-section of at least
2.5 mm² Cu.
– It has a second protective conductor in parallel with the same cross-section.
– It complies with the local regulations for equipment with increased leakage current.
Cables laid within control cabinets or closed machine housings are considered to be
1)
adequately protected against mechanical damage.
WARNING
WARNING
are specified in the dimension drawings.
Motor Modules
6.2 Safety information
1)
201