Forming the DC link capacitors

Description
If the Power Module, Basic Line Module, Active Line Module, and Motor Module have not
been used for more than two years, the DC link capacitors must be reformed. If this is not
carried out, the units could be damaged when the DC link voltage is connected under load.
If the cabinet is commissioned within two years of its date of manufacture, the DC link
capacitors do not need to be reformed. The date of manufacture can be taken from the serial
number on the rating plate.
Note
Storage period
It is important that the storage period is calculated from the date of manufacture and not from
the date that the equipment was shipped.