Vertical Installation - Siemens Sinamics S120 Manual

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

8.3.3

Vertical installation

The SINAMICS S120 liquid-cooled devices are suitable for vertical installation in a cabinet
with a minimum width of 400 mm.
A partition must be installed between the cabinets housing and the SINAMICS device to
ensure that the device is adequately ventilated.
The dimensions for the installation heights of the partition are specified in the following table.
Table 8- 4
Power Module FL
Power Module GL
Basic Line Module FBL
Basic Line Module GBL
Active Line Module FXL, Motor Module FXL
Active Line Module GXL, Motor Module GXL
Active Line Module HXL, Motor Module HXL
Active Line Module JXL, Motor Module JXL
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
8.3 Cabinet installation, vertical and horizontal installation
Installation height of the partition from the lower side of the device (from the lower edge
of the device)
Type
Cabinet design and EMC
Installation height of the
partition
[mm]
140
290
480
910
150
480
340
800
303