Siemens Sinamics S120 Manual page 157

Liquid-cooled chassis power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Table 5- 11
Technical data for Basic Line Modules, 500 ... 690 V 3 AC
Article number
Rated power
- At I
(50Hz 690V)
L DC
- At I
(50Hz 690V)
H DC
- At I
(50Hz 500V)
L DC
- At I
(50Hz 500V)
H DC
- At I
(60Hz 575V)
L DC
- At I
(60Hz 575V)
H DC
DC-link current
- Rated current I
N DC
- Rated current I
L DC
- Base load current I
H DC
- Maximum current I
max DC
Input current
- Rated current I
N E
- Maximum current I
max E
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
- Fan supply voltage
- DC-link voltage
Electronics current consumption (24 V DC)
Cooling method
Power loss, max.
2)
- At 50 Hz 690 V
- At 60 Hz 575 V
- Dissipated to the ambient air
Max. coolant temperature
- Without derating
- With derating
Rated flow rate
Pressure drop, typical
at the rated flow rate
3)
Liquid volume of integrated heat exchanger
DC-link capacitance
- Basic Line Module
- Drive line-up, max.
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
6SL3335–
kW
kW
kW
kW
HP
HP
A
A
A
A
1)
A
A
V
ACrms
Hz
V
DC
V
AC
V
DC
A
kW
kW
kW
° C
° C
l/min
Pa
dm³
µF
µF
dB(A)
mm²
mm²
mm²
1TG34–2AA3 1TG37–3AA3 1TG41–3AA3 1TG41–7AA3
355
630
275
475
245
420
200
345
395
705
305
530
420
730
403
700
328
570
630
1095
340
600
510
900
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
47 ... 63 Hz
24 (20.4 ... 28.8)
230 (195.5 ... 264.5)
1.35 x U
(partial load) / 1.32 x U
line
0.7
0.7
Liquid cooling with integrated aluminum heat exchanger
1.76
3.09
1.76
3.09
0.21
0.38
45
45
50
50
9
9
70000
70000
0.45
0.45
4800
7700
38400
61600
54
54
Flat connection for M12 screw
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
Line Modules
5.2 Basic Line Modules
1100
1370
840
1070
750
950
610
775
1230
1530
940
1195
1300
1650
1248
1584
1014
1287
1950
2475
1070
1350
1605
2025
(full load)
line
0.7
0.7
5.09
6.25
5.09
6.25
0.43
0.55
45
45
50
50
12
12
70000
70000
0.79
0.79
15500
19300
124000
154400
56
56
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
157

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simanics s120

Table of Contents