1.

Introduction

1.1.

Safety rules and advice to regularly test alarms

To use the Octalarm-Touch properly, please read and follow these safety rules:
• mount the device on a solid panel or wall;
• the Octalarm-Touch must be mounted below 2 meter height;
• protect the Octalarm-Touch against a surge by using a grounded power connection;
• do not use an outdoor ethernet connection directly, instead use a surge protected switch or router;
• use the Octalarm-Touch in an indoor setting, the device needs to be protected from direct weather
exposure;
• the device operates at temperatures between 0°C and +50°C. Using the Octalarm-Touch outside this
temperature range may damage the system;
• this equipment is not suitable for use in locations where children are likely to be present;
• the recycling and/or disposal will have to be done by following the guidelines stated in this manual.
Battery handling guide
• Only use the Adésys Octalarm-Touch type battery. There is a risk of explosion if the battery is replaced
by an incorrect type.
• Do not expose battery to temperature over +85°C or an open flame.
• Do not damage the Octalarm-Touch battery. Do not damage the unit by dropping, deforming,
impacting, cutting or penetrating with a sharp object.
• Do not charge or discharge damaged battery.
• Keep the battery away from direct contact with liquids. Do not use if battery is wet or moist is visible;.
• The recycling and/or disposal will have to be done by following the guidelines stated in this quickstart.
1.2.

Alarm safely

We advise you to obtain a safe and reliable alarm
• to enter multiple contacts of persons and to make them part of the alarm handling;
• using multiple alarm methods, such as speech and app, together;
• tick critical alarms as such, so that they are ALWAYS logged out. This gives the app a higher attention
value,
see chapter "6.1.1. Alarm settings (left side)";
• to increase the number of repetitions after acceptance
• adjust the default setting "waiting time between repetitions" (default at 30 minutes) to the urgency of
the alarm (for example 10 minutes)
• work with short alarm delays (default "delay before active" at 5 seconds and "delay after recovery" at 2
seconds)
see chapter "6.1.1. Alarm settings (left side)"
Periodic testing of alarms
Octalarm-Touch has been developed and manufactured with great care. However, given the importance
of good alarms, it is recommended that you test the alarms regularly (e.g. once a week). This will not only
test the proper operation of the Octalarm-Touch, but also the telephone connections. An example of a
good test is to briefly remove the mains plug, which will cause a power failure to be called out. See also
chapter "5.1. Adding and editing contacts" under Contacts for more test options.
1.3.

Maintenance

For an optimal use of the Octalarm-Touch the following maintenance rules must be applied:
• change the battery every 2 years;
• keep the screen clean of grease, water and dust;
• the calculated lifespan is 10.64 years. Replace the Octalarm-Touch after this period has elapsed.
1.4.

Storage and transport

• Store and transport the product on a flat surface.
• There must be no flammable or explosive materials nearby.
• The temperature must be within the 0°C and +85°C range.
• Do not store this product in a place exposed to direct sunlight.
• To preserve the internal clock, the Octalarm-Touch may not be stored for more than a year.
1.5.

Malfunctions and repairs

When a fault has occurred please contact Adésys service helpdesk. By opening the Octalarm-Touch the
warranty is void. Repairing the Octalarm-Touch is only allowed by Adésys appointed experts.
1.6.

Recycling and disposal

The Octalarm-Touch is an electronic device. Electronic devices should not be mixed with general
household waste. For disposal of your Octalarm-Touch, please contact your installer or Adésys.
Manual Octalarm-Touch | Back to
see chapter "6.1.1. Alarm settings (left side)"
.
index
see chapter"6.1.1. Alarm settings (left side)"
;
;
Page 4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Octalarm-Touch and is the answer not in the manual?

Questions and answers

Related Products for Adesys Octalarm-Touch

Table of Contents