Application Selections; Setting The Carrier Frequency - YASKAWA Varispeed E7 Instruction Manual And Parameter Description

Hvac frequency inverter
Hide thumbs Also See for Varispeed E7:
Table of Contents

Advertisement

Application Selections

Setting the Carrier Frequency

Using the following constants the carrier frequency setting can be fitted to the applications requirements.
Related Constants
No.
Con-
stant
No.
C6-02
Carrier frequency selection
C6-03
Carrier frequency upper limit
C6-04
Carrier frequency lower limit
Carrier frequency
C6-05
proportional gain
* 1. The factory settings depend on the Inverter capacity.
* 2. The setting ranges depend on the Inverter capacity.
* 3. Can be set and referenced only when C6-02 is set to F.
When selecting the carrier frequency, observe the following precautions:
If the wiring distance between Inverter and motor is long: Set the carrier frequency low. (Use the following
values as guidelines.
C6-02 (carrier frequency)
setting
If speed and torque vary at low speeds: Set the carrier frequency low.
If Inverter noise is affecting peripheral devices: Set the carrier frequency low.
If leakage current from the Inverter is large: Set the carrier frequency low.
If metallic noise from the motor is large: Set the carrier frequency high.
The carrier frequency can be set to vary depending on the output frequency as shown in the following dia-
gram, by setting C6-03 (Carrier Frequency Upper Limit), C6-04 (Carrier Frequency Lower Limit), and
C6-05 (Carrier Frequency Proportional Gain).
-2
6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Selects the carrier frequency.
Select F to enable detailed settings using constants C6-03 to
C6-05.
Sets the upper and lower carrier frequency limits in kHz.
Set the carrier wave gain as shown below.
Carrier frequency
K is the coefficient determined by the set value in
C6-03.
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz : K = 2
5.0 kHz > C6-03: K = 1
Wiring Length
50 m or less
0 to 6 (15 kHz)
Details
Output frequency x
(C6-05) x K
Output frequency
(Maximum output frequency)
100 m or less
0 to 4 (10 kHz)
Changes
Setting
Factory
Access
During
Range
Setting
Level
Opera-
tion?
*1
0 to F
No
Q
6
2.0 to
15.0 kHz
No
A
15.0
*1
*2 *3
0.4 to
15.0 kHz
No
A
15.0
*1
*2 *3
00 to 99
00
No
A
*3
Over 100 m
0 to 2 (5 kHz)