Hunting-Prevention Function

The hunting-prevention function suppresses hunting when the motor is operating with a light load.
If high response has the priority to vibration suppression this function should be disabled (N1-01 = 0).
Related Constants
Con-
stant
Name
Number
Hunting-prevention function
N1-01
selection
N1-02
Hunting-prevention gain
Adjusting the Hunting-Prevention Gain (N1-02)
Normally it is not necessary to change this setting. Adjust the value under the following circumstances:
If vibrations occur under light load condition increase the setting.
If the motor stalls reduce the setting.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
0: Hunting-prevention function disabled
1: Hunting-prevention function enabled
Set the hunting-prevention gain multiplication factor.