MANAGING ADDITIONAL ZONE
6.4 Setting zone's climatic curve parameters
(accessible only with installer password)
Menu → "Settings" → "Zone Clim. Curve"
− press the ► key so that the number is highlighted on the
right of the word "Zone";
Ext. Zone Climatic Curve
"
External Zone
"
"
− use the ▲ and ▼ keys to change the zone number;
− press the ● key.
The following is displayed:
Outdoor reset
"
"
90
0
-15
T Outside [°C]
"
Par. No.
Description
Design Supply
Zone heating maximum setpoint
Temp.
Baseline Supply
Zone heating minimum setpoint
Temp.
Baseline Out-
Maximum external temperature
door Temp.
Design Outdoor
Minimum external temperature
Temp.
T_Switch off Summer/winter switching
It blocks the heating request when the external temperature is
greater than this setpoint.
Comp. Parameter T. @ T.ext. Max
During in-between seasons, when the external temperature
gets close to the maximum limit set (T. Ext. Max.), the delivery
temperature calculated in the climatic curve could be different
from the one suitable to meet the request. This parameter per-
forms a non-linear correction of climatic curve to compensate
such difference.
Delivery Temp.
(°C)
Max. Heating Set.
Min. Heating Set.
Baseline Outdoor Temp.
Min Outdoor Temp.
"
1
Des. Supply T.
82.0
"
"
Bas. Supply T.
40.0
"
"
WW Shutdown
21.0
"
"
Bas. Outd. T.
21.0
35
"
"
Des. Outd. T.
-4.0
"
"
"
Comp. T. @ T.ext. Max
Outdoor Temp. (°C)
Shutdown Temp.

6.5 Programming the zone

By default the schedule timer is disabled.
In fact, to start a request from the zone just close the contact
of the zone request. In this case the thermal module (or the
cascade of thermal modules) will start with a setpoint equal to
the value calculated on the zone climatic curve increased by the
"Zone Extra Setpoint" value and the mix valve will modulate to
maintain the delivery temperature of the zone at the calculated
setpoint.
If there is no external sensor, the delivery setpoint of the ther-
mal unit will be equal to the maximum setpoint of the climatic
curve.
To activate zone programming:
Menu → "Settings" → "Clock Settings"
Settings
"
"
Clock Settings
"
Appliance Configuration
°C
"
"
"
°C
External Zone Settings
"
"
"
°C
Ext. Zone Climatic Curve
"
"
°C
"
"
"
°C
Confirming with ● the following screen is displayed:
"
"
Clock Settings
"
CH Clock
"
"
DHW Clock
"
CH Ext. Zones Clock
"
− with the ▲ / ▼ keys select "CH Zones clock"
− with the ► key move to "Disabled", change it to "Ena-
bled" with the ▲ / ▼ keys
− confirm with the ● key
Go to:
Menu → "Clock program"
Confirming with the ● key:
Clock Program
"
Program CH Zone Ext.
"
Program Group
"
Holiday Settings
"
Season Settings
"
At this point select the number of the zone to be programmed
and confirm with the ● key.
External Zone
"
Program Comfort Period
"
Comfort Setpoint
"
ECO Setpoint
"
Out of interval setpoint
"
124
p
"
"
"
"
"
Disabled
"
Disabled
"
"
Disabled
"
"
"
1
"
1
"
"
"
1
"
1
"
20.0
"
5.0
°C
"
"
Anti Fr
"
"
"
"
"