Nr. dis-
Par.
Menu
played
No.
Display
DHW Tank
Defines the hysteresis to stop the domestic hot
M1
37
Hyst. Up
water demand.
Defines the primary circuit's set-point increase in
DHW Tank
M1
38
degrees compared to the temperature set for the
Supply Extra
domestic hot water tank.
DHW Tank
Defines the primary circuit's restart hysteresis in
M1
39
Supp Hyst
modes 1 and 2 of domestic hot water (valid both for
Dn
cascade and stand-alone applications).
DHW Tank
Defines the primary circuit's shut-off hysteresis in
M1
40
Supp Hyst
modes 1 and 2 of domestic hot water (valid both for
Up
cascade and stand-alone applications).
Defines the value of a storage cylinder's delta T re-
quired for temperature maintenance. For instance,
if set at 3 degrees, when the storage cylinder is at
a set-point value minus 3 degrees, the boiler is
DHW Tank
switched on at minimum power to maintain the
M1
41
Hold Warm
temperature to the set-point plus hysteresis. If this
parameter is kept the same as Par. 36, this function
is inactive and the boiler is switched on at the
maximum power envisaged for the domestic hot
water's circuit.
Defines the priority type:
0 = Time: time priority between the two circuits
defined by Par. 43;
1 = Off: priority for CH;
M1
42
DHW Priority
2 = On: priority for DHW;
3 = Parallel: parallel priority managed on the basis
of the primary circuit's temperature compared to
the heating circuit's set-point.
DHW stor-
Defines the Accumulation sanitary Setpoint in
M1
115
age tank
mode 1
setp.
DHW Max.
Establishes the time in minutes during which
M1
43
Priority
priority is alternatively allocated to the DHW and CH
Time
circuits when Par. 43 is set to "time" mode.
Establishes the overrun time in seconds for the
domestic hot water mode with the boiler in stand-
DHW Pump
M1
44
alone operation; cascaded operation defines the
Overrun
module's overrun after switch-off due to ther-
moregulation.
DHW Tank
Defines the proportional term for modulation dur-
M1
45
PID P
ing operation of the DHW storage tank.
DHW Tank
Defines the integral term for modulation during
M1
46
PID I
operation of the DHW storage tank.
DHW Tank
Defines the derivative term for modulation during
M1
47
PID D
operation of the DHW storage tank.
DHW tank
Establishes the DHW storage tank set-point Par. 35
M1
48
set-point
in mode 2.
Fan Speed
Defines the number of fan rpm at max. power (it
M1
92
Maximum
depends on the model and is defined at Par. 98).
Defines the number of fan rpm at minimum power
Fan Speed
M1
93
(it depends on the model and is defined at Par.
Minimum
98).
Defines the number of fan rpm when the boiler
Fan Speed
M1
94
is switched on (it depends on the model and is
Ignition
defined at Par. 98).
The value of this parameter is defined by Par. 97.
Prog. Input
0 = Disabled
M1
116
1.
1 = Minimum water pressure switch
3 = Flue gas pressure switch
The value of this parameter is defined by Par. 97.
0 = Disabled
Prog Input
1 = DHW flowmeter
M1
117
2.
2 = DHW flow switch
3 = Heating flowmeter
4 = Heating flow switch
Description
35
Default set-
Range
ting
0...20
5
0...30
15
0...20
5
0...20
5
0...10
5
0...3
2
40...71
57
1...255
30
Min.
0...900
60
0...1255
100
0...1255
500
0...1255
0
40...71
50
Defined by
0...12750
RPM
Par. 98
Defined by
0...12750
RPM
Par. 98
Defined by
0...12750
RPM
Par. 98
0,1,3
0
0...4
0
INSTALLATION
Access
UM
Category
type
°C
I
DHW
°C
I
DHW
°C
O
DHW
°C
O
DHW
°C
O
DHW
I
DHW
°C
U
DHW
I
DHW
Sec.
I
DHW
O
DHW
O
DHW
O
DHW
°C
U
DHW
I
General
I
General
I
General
I
General
I
General