SYSTEM MANAGER
Register
Access Description
number
510
X
X
511
X
X
In the "Note" column, the registers marked with "V" can be
written on an ongoing basis (and be used for dynamic size con-
trol). Registers marked with "NV", on the other hand, can be
overwritten only for a limited number of times (around 10,000
times with an average of twice a day).
Service reminder
Access
Register
number
L
S
1500
X
1501
X
33000
X
33001
X
STATUS table
Nr.
Name
0
STANDBY
10
ALARM
14
BLOCK
15
FROST_PROTECT Frost protection on
16
CH_DEMAND
17
RESET_STATE
STORAGE_DE-
18
MAND
DHW_TAP_DE-
19
MAND
20
DHW_PRE_HEAT Pre-heating demand
STORE_HOLD_
21
WARM
GENERAL_
22
PUMPING
Auto-
matic
Note
conver-
sion
Minimum
value that
can be as-
NV
Yes
signed to the
heating set-
point (Par. 23)
Night-time
attenuation
NV
Yes
(Par. 28)
Automatic
Description
conversion
Hours elapsed
from the last
maintenance
activity
Hours from the
next mainte-
nance activity
Hours elapsed
from the last
maintenance
activity
Hours from the
next mainte-
nance activity
Description
Standby
Non-volatile lockout error
Volatile lockout error
Heat demand
Reset
DHW demand
Imm. DHW demand.
Holding desired storage temperature
General pump ON
STATE table
Nr.
Value
range
0
RESET_0
1
2
STANDBY_0
Depends
on °C/°F
3
PRE_PURGE
units
4
PRE_PURGE_1
Depends
5
SAFETY_ON
on °C/°F
6
SAFETY_OFF
units
7
8
9
BURN_0
SHUT_DOWN_
10
RELAY_TEST_0
Value
range
SHUT_DOWN_
11
RELAY_TEST_1
0...65534
12
POST_PURGE_0
hours
13
POST_PURGE_1
14
PUMP_CH_0
.. 0...2000
15
PUMP_CH_1
0...65534
16
PUMP_HW_0
hours
17
PUMP_HW_1
18
ALARM_1
.. 0...2000
19
ERROR_CHECK
20
BURNER_BOOT
CLEAR_E2PROM_
21
STORE_BLOCK_
22
23
WAIT_A_SECOND Waiting before entering another state
133
Name
Description
Initialisation of reset variables
RESET_1
Reset
Standby
Initialisation of pre-purging variables
Pre-purging
ON safety relay test
OFF safety relay test
IGNIT_0
Initialisation of ignition variables
IGNIT_1
Start-up
The module is ON
Initialisation of variables to check
safety devices and gas valve
Safety and gas valve test relay
Initialisation of post-purging varia-
bles
Post-purging
Initialisation of heating pump varia-
bles
Heating pump
Initialisation of DHW pump variables
DHW pump
Non-volatile lockout error
Volatile lockout error
Restart of board
Cancel error E2PROM
ERROR
Save error
ERROR
MODBUS CONNECTION