System parameters Block diagram 2

9
See section "Commissioning and maintenance" for a de-
tailed description of how the parameters work
MANAGING
Functions:
− Reads system sensor (SS)
− Controls thermal unit two-way valve (V1)
− Controls system pump (PS)
− Controls DHW pump (PB) instead of the LPG gas solenoid
valve (VLPG)
− Reads storage tank sensor (SB)
− Manages control of mixed zone 2 zone management (ZM)
device via bus. Up to a maximum of 16 devices can be
managed.
Programmable outputs and inputs parameter configuration (*)
(If Par. 97 = 11-21-22-23-24-25 - Stand alone configuration)
Par.
Description
Parameter setting
No.
Progr.ble
3 = DHW pump (**)
125
outp. 1
Progr.ble
187
4 = System pump (PS)
outp. 5
Progr.ble
128
1 = General pump (V1)
outp. 4
122 Prog Input 7
3 = System sensor (SS)
188 Prog Input 9
1 = DHW sensor (SB)
(*)
Do NOT change the factory setting of parameter 97
(**)
In place of the fuel shut-off valve VPLG
Configuration of parameters for INAIL kit (***)
Par.
Description
Parameter setting
No.
2 = Water pressure
123 Prog Input 8
117
Prog Input 2
3 = Heating flowmeter
(***)
An INAIL kit is required for each thermal unit
Terminals No.
M02
16-17-18
M02
9-10-11
M02
13-14-15
M01
9-10
M01
13-14
Terminals No.
M01
27-28
switch
M01
21-22-23
CONFIGURATION OF CASCADED THERMAL UNITS
Hardware configuration
S1 = OFF (not used)
DIPSWITCH = 10000000
Configuration of boiler parameters
Par.
Description
No.
73
Boiler Address
147
Number of Units
184 No. Active DHW units
7
CH Hysteresis
35
DHW mode
135
Mod. Pump Type
136
Mod. pump mode
140
Minimum Flow
Configuration of cascade parameters
Par.
Description
No.
148
Power Mode
152
PwrMode2 Min Power
153
PwrMode2 Hysteresis
84
Module Rotation Interval
74
Emergency mode setpoint
91
Parameter setting
- "Managing" (if the cascade
sensor is used SC)
- "Stand-Alone" (if the cascade
sensor is not used SC)
Set the total number of cascaded
units (from 2 to 8)
0 to 8 (Number of active units for
DHW production)
7°C
Choose from:
1 = Water heater with probe
2 = Water heater with thermostat
2 = Grundfos (choose according to
need)
Fixed 90% (according to need)
5 l/min
Parameter setting
Choose from:
2 = Maximum number of
burners
3 = Minimum number of
burners
4%
40%
5 days
50 (according to need)