INSTALLATION
Nr. dis-
Par.
Menu
played
No.
Display
Sets the value of the temperature difference (Delta
T) between the module's delivery and return tem-
perature. For a Delta T value ranging between Par.
12 and (Par. 12) +8°C, the module reduces its power
Hx diff.
in a linear fashion until it reaches the minimum
M1
12

Minimum

power. The minimum power is maintained until
reaching (Par. 12) +8°C+5°C, after which the module
switches off for a period of time equal to the value
attributed to Par. 13; at the end of this time interval,
the module switches on again.
Hx Diff.
Defines the restart time after reaching the Delta T
M1
13
Max. Wait
limit between delivery and return.
Time
Max. Power
M1
14
Sets the heating's % max. power.
CH
Min. Power
M1
15
Sets the heating's % min. power.
CH/DHW
Defines the proportional parameter for modulation
M1
16
CH PID P
during heating operation.
Defines the modulation integral term during heat-
M1
17
CH PID I
ing operation.
Defines the modulation derivative term during
M1
18
CH PID D
heating operation.
Design Sup-
Defines the max. set-point at the minimum out-
M1
19
ply Temp.
door temperature for climatic regulation.
Defines the minimum outdoor temperature to
Design Out-
M1
20
which the maximum set-point can be associated
door Temp.
for climatic regulation.
Baseline
Defines the minimum set-point at the maximum
M1
21
Supply
outdoor temperature for climatic regulation.
Temp.
Baseline
Defines the maximum minimum outdoor tem-
M1
22
Outdoor
perature to which the minimum set-point can be
Temp.
associated for climatic regulation.
Design
Limits the minimum value that can be assigned to
M1
23
Supply Min.
the set-point in heating mode (does not apply to
Limit
heating mode 4).
Design
Limits the maximum value that can be assigned to
M1
24
Supply Max.
the set-point in heating mode (does not apply to
Limit
heating mode 4).
Warm
Defines the temperature at which climatic regula-
M1
25
Weather
tion is switched off.
Shutdn
Establishes the set-point temperature increase
Boost Temp
delta T, if the heat demand in heating mode is not
M1
26
Increment
satisfied after the time interval specified in Par. 27
(applies only to stand-alone mode).
Defines the time interval after which the set-point
Boost Time
M1
27
is increased as defined in Par. 26 (applies only to
Delay
stand-alone mode).
Used in heating mode Par. 1= 2 or 3. Establishes
Night Set-
by how many degrees the delivery set-point is
M1
28
back Temp.
reduced when the RT (room thermostat/heat de-
mand) contact is closed.
Establishes the domestic hot water circuit's opera-
tion mode.
M1
35
DHW mode
0 = Disabled
1 = Water heater with probe
2 = Water heater with thermostat
Max. Power
Defines the domestic hot water circuit's % max.
M1
113
DHW
power.
Min. Power
Defines the domestic hot water circuit's % mini-
M1
114
DHW
mum power.
DHW Tank
Defines the hysteresis to initiate the domestic hot
M1
36
Hyst. Down
water demand.
Description
34
Default set-
Range
ting
10...60
40
10...250
30
Sec.
50...100
100
1...30
1
0...1275
100
0...1275
250
0...1275
0
30...90
80
-25...25
0
30...90
40
0...30
20
4...82
30
27...90
80
0...35
22
0...30
0
1...120
20
Min.
0...30
10
0...2
0
50...100
100
1...30
1
0...20
5
Access
UM
Category
type
°C
O
General
O
General
%
I
Heating
%
I
Heating
O
Heating
O
Heating
O
Heating
°C
U
Heating
°C
U
Heating
°C
I
Heating
°C
I
Heating
°C
I
Heating
°C
I
Heating
°C
I
Heating
°C
I
Heating
I
Heating
°C
I
Heating
I
DHW
%
I
DHW
%
I
DHW
°C
I
DHW