Technical Specifications Of Stack; Connection To The Stack - Riello TAU Unit 50 Installation And Maintenance Manual

Hide thumbs Also See for TAU Unit 50:
Table of Contents

Advertisement

TAU
Unit
50
A
B
C
D
1 - Exhaust flue duct
2 - Rear flue gas dis-
charge (optional)
Flue gas discharge
duct through-wall
hole
Air intake duct
through-wall hole
Coaxial flue gas dis-
charge/air intake for
type C configurations
(optional)
Coaxial air intake/flue
gas discharge duct
through-wall hole
A
2
1
C
Unit of
TAU
TAU
TAU
meas-
Unit
Unit
Unit
70
100
115
ment
100
515
100
763
764
80
110
Ø mm
80
110
Ø mm
100
130
Ø mm
100
Ø mm
80/125
110/160
Ø mm
150
180
Ø mm
2.8.1

Technical specifications of stack

The stack must satisfy the following requirements::
− It must be constructed from materials that are imper-
meable to flue gases and that offer lasting resistance to
mechanical stress, heat and the action of the products of
combustion and condensate
− It must be vertical, free of restrictions and contain bends
of no more than 45°
− It must be suitable for the specific operating conditions
of the boiler and must be CE marked
− It must be of adequate dimensions to ensure draught
and venting properties suitable for the needs of the boil-
er
− It must have adequate external insulation to prevent
condensation and the cooling of flue gases
− the stack must have a dedicated condensate drain sys-
tem at the bottom.
9
The diameter of the smoke duct must never be smaller than
the diameter of the flue gas duct of the thermal unit.
9
In configuration B23, the stack must guarantee the mini-
mum draught specified by applicable technical standards,
assuming zero pressure at the boiler's flue gas exhaust.
2.8.2

Connection to the stack

The boiler must be connected to the stack using rigid flue pipes
that are resistant to heat, condensate and mechanical stress. All
joins must be sealed and the finished flue must be insulated.
The near-horizontal section of flue pipe must have a slope of at
least 5° towards the boiler and must also be properly insulated.
In long near-horizontal sections of flue pipe (L>1 m), install a
condensate drain system near the boiler exhaust (as shown in
the figure) to drain off any condensate forming in this section
of flue.
The diameter of the stack must always be greater than that of
the flue pipe from the boiler's exhaust fitting. To change direc-
tion, use a T section with an inspection cap to permit easy access
for cleaning inside the pipe. After cleaning, always make sure
that inspection caps are replaced tightly and that their seals are
undamaged and efficient.