Table 2.3 Ac Cable Specifications For The Primequest 480/440 Main Unit - Fujitsu PRIMEQUEST 480 Installation Planning Manual

Hide thumbs Also See for PRIMEQUEST 480:
Table of Contents

Advertisement

CHAPTER 2 Connection Reference
2.4
Input Power Supply Unit Connections
The following table lists the connection specifications for the input power supply unit.
PRIMEQUEST 480/440 main unit (2.4.1)
Cables between PCI_Box and ACS in the extended I/O cabinet (2.4.2)
Cables between ACS in the extended I/O cabinet and power distribution board
(2.4.3)
2.4.1
PRIMEQUEST 480/440 main unit
Table 2.3 lists the specifications for connecting the input power supply unit to the
PRIMEQUEST 480/440 main unit.

Table 2.3 AC cable specifications for the PRIMEQUEST 480/440 main unit

Destination
JAPAN
Outside Japan
(for North
America)
FSC
Note:
2-32
AC cable
specification
CA06501-G041
CA06501-G042
CA06501-G043
Use the supplied accessory AC cable to connect the main unit. Do not use
the accessory AC cable for other products.
Plug type
Three-prong
Power-receiving outlets must be
hook-type plug
available.
with grounding
Three-prong hook-type receptacle
electrode(30A-
with grounding electrode (30A-
250VAC)NEMA
250VAC outlet)
standard name:
NEMA L6-30
L6-30P
Embedded type: 3320-L6
(American Denki)
Exposed type: 4321-L6
(American Denki)
NEMA L6-30P
NEMA L6-30R (only for North
America)
30A-220V
IEC309 (32A)
IEC309 (32A)
Remarks