Table 1.5 Installation Specifications (Air Conditioning 2) - Fujitsu PRIMEQUEST 480 Installation Planning Manual

Hide thumbs Also See for PRIMEQUEST 480:
Table of Contents

Advertisement

CHAPTER 1 Installation Reference
*4
*5

Table 1.5 Installation specifications (air conditioning 2)

No.
Product
1
PRIMEQUEST 440 main
unit
(Type name: MC4A0P111)
2
PRIMEQUEST 480 main
unit
(Type name: MC5A0P111)
3
Extended power cabinet
(Type name: MC-57DP11,
MC-77UGD1) (*2)
4
Extended I/O cabinet
(Type name: MC-77RK11)
(*3)
5
PCI_Box
(Type name: MC-07PB11)
*1
*2
*3
1-12
In the extended power cabinet, the fans operate at low speeds in standby
mode and at high speeds in operating mode.
Value when eight PCI_Boxes are mounted
Sound power
Noise [dB(A)]
level [B(A)]
70 or less
8.5 or less
70 or less
8.5 or less
Included in the
Included in the
main unit
main unit
Included in the
Included in the
main unit
main unit
Included in the
Included in the
main unit
main unit
"Not operating" means the unit is stored.
In the extended power cabinet, the fans operate at low speeds in standby
mode and at high speeds in operating mode.
This value assumes that eight PCI_Boxes are mounted.
Allowable vibration [m/S
Operating
Not operating
(including
(*1)
standby)
2.5
4.0
(Synthetic
(Synthetic
seismic vibration)
seismic vibration)
2
]
Allowable
Remarks
3
dust [mg/m
]
0.15
5 SBs or 5
IO_Units or more
4 SBs or 4
IO_Units or less
5 SBs or 5
IO_Units or more
4 SBs or 4
IO_Units or less
C122-H001-02EN