Sensor Type Set Up - Danfoss DEVIreg Multi Installation And User Manual

7 channel din-rail programmable controller
Hide thumbs Also See for DEVIreg Multi:
Table of Contents

Advertisement

Installation and User Guide
Line of the Main screen with 1S mode data for one Channel is shown on the picture below:

4.4.3.2 Sensor Type set up

1S control mode can be set up with different 8 types of temperature sensors .
Sensor unit can be selected via software connected to Channel's analog inputs AI1-AI7 between:
NTC15k (15 kOhm @ 25 °C), NTC10k (10 kOhm @ 25 °C), NTC5k (5 kOhm @ 25 °C), NTC2k
(2 kOhm @ 25 °C), NTC100 (100 kOhm @ 25 °C), NTC16k (16,7 kOhm @ 100 °C), PT1000
(1000 Ohm @ 0 °C), Ni100 (100 Ohm @ 0 °C) .
Setting of Sensor type can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Sensor
type – {Enter – Up/Down ( PT1000/ NTC10k/ NTC100/ Ni100/ NTC2K/ NTC16k/
NTC5k/ NTC15k) }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Sensor
type – {Enter – Up/Down ( PT1000/ NTC10k/ NTC100/ Ni100/ NTC2K/ NTC16k/
NTC5k/ NTC15k) }
NB: Setting is possible/visible for Active Channels only.
Chosen Sensor type can be found in the Channel Data screens with the following menu
sequence:
EN: Main Screen – Down .
EN: Main Screen – Down.
20
DEVIreg™ Multi
Channel
Real sensor
number
Temp.
Heating
Set up
status: On or Of
Temp.