Temperature Limits - Emerson MicroMotion HPC010 Installation Manual

High pressure coriolis flow meters
Table of Contents

Advertisement

Installation Manual
MMI- 20032352
2.5

Temperature limits

Model
HPC010
HPC015
Notes
In all cases, the electronics cannot be operated where the ambient temperature is
below -40 °F (-40.0 °C) or above 140 °F (60.0 °C). If a sensor is to be used where the
ambient temperature is outside of the range permissible for the electronics, the
electronics must be remotely located where the ambient temperature is within the
permissible range, as indicated by the shaded area of the temperature limit graphs.
Temperature limits may be further restricted by hazardous area approvals. Refer to the
hazardous area approvals documentation shipped with the sensor or available from
www.emerson.com/flowmeasurement.
Installation Manual
Component
Process fluid temperature
Ambient temperature
Process fluid temperature
Ambient temperature
Planning
March 2020
Limit
-58 °F (-50 °C) to 257 °F
(125.0 °C)
-40 °F (-40.0 °C) to 140 °F
(60.0 °C)
-50.8 °F (-46 °C) to 392 °F
(200 °C)
-40 °F (-40.0 °C) to 140 °F
(60 °C)
9