DC-UPS with Integrated Battery - 24V, 10 A
Relay Contacts and Inhibit
Input
Contact
State
Ready
The inhibit input disables buffering. In normal mode, a static signal is required. In buffer mode, a pulse
with a minimum length of 250 ms is required to stop buffering. The inhibit is stored and is reset by
cycling the input voltage.
14
The DC-UPS is equipped with relay contacts and signal inputs for remote
monitoring and controlling of the unit.
Relay Contacts
Contact
State
Ready
Contact is closed when battery is charged more than 85%, no wiring failure are recognized, input
voltage is sufficient, and inhibit signal is not active.
Buffering
Contact is closed when unit is buffering.
Replace battery
Contact is closed when the unit is powered from the input and the battery quality test (SOH test)
reports a negative result.
Attribute
Description
Relay Contact ratings
Max
Min
Isolation voltage
Max
Signal Input
Attribute
Description
Signal voltage
Max
Signal current
Max
Inhibit threshold
Min
Max
Isolation
Nom
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
60V DC, 0.3 A, 30V DC, 1 A, 30V AC, 0.5 A resistive load
1 mA at 5V DC min.
500V AC, signal port to power port
35V DC
6 mA, current limited
6V DC, buffering is disabled above this threshold level
10V DC
500V AC, signal port to power port