Input - Allen-Bradley 1606-XLS240-UPSC Reference Manual

Dc-ups with integrated battery - 24v, 10 a
Table of Contents

Advertisement

DC-UPS with Integrated Battery - 24V, 10 A

Input

Attribute
Input voltage
Input voltage ranges
Allowed input voltage ripple
Allowed voltage between input and
earth (ground)
Turn-on voltage
(1)
Input current
External capacitors on the input
(1) The unit shows 'Check Wiring' with the red LED and buffering is not possible.
(2) The total input current is the sum of the output current, the current that is required to charge the battery during the charging process and the current that is needed to supply the
DC-UPS itself. See
Figure
(3) This is the input current and not the current that flows into the battery during charging. See for the battery current.
Figure 3 - Input Voltage Range
6
Figure 2 - Markings
IND. CONT. EQ.
UL 508
Description
Nom
24V DC
Nom
22.5...30V DC
30...35V DC
35V DC
0...22.5V DC
Max
1.5V pp
1V pp
Max
60V DC or 42.4V AC
Typ
22.8V DC
Max
23V DC
Typ
120 mA
Typ
1.1 A
No limitation
4. This calculation does not apply in overload situations where the DC-UPS limits the output current. See
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
UL 60950-1
Marine
Continuous operation, see
Temporarily allowed, no damage to the DC-UPS.
Absolute maximum input voltage with no damage to the DC-UPS.
The DC-UPS changes to Buffer mode and delivers output voltage
from the battery if the input is above the turn-on level before and
all other buffer conditions are fulfilled.
Bandwidth < 400 Hz
Bandwidth 400 Hz to 1 kHz
The output does not switch On if the input voltage does not
exceed this level.
Internal current consumption
Current consumption for battery charging in constant current
mode at 24V input. See
Figure
Figure
Figure 4 - Input Current, Definitions
Class 1 Div 2
Figure
3.
(2)
(3)
13.
5.