Bulletin 1609 Industrial Uninterruptible Power Supply

Dry I/O Contacts

There is one Remote Enable/Disable Switch connection and 3 Dry I/O Contacts available on the front of the
UPS. Do not apply external power to the Remote Enable/Disable Switch; however, the 3 sets of Dry Contacts
required external power supplies (Contacts Rating is 1A/24 Vdc). Each of the Dry Contacts is used to provide a
remote status indication of the UPS as follows:
8 7 6 5 4 3 2 1

USB Communication Port

Manual or Remote Enable / Disable of UPS Output Selection
The 1609-B UPS output is designed to be manually or remotely Enabled or Disabled. User is required to
enable or disable the remote function switch on the front panel.
REMOTE FUNCTION
DISABLE

Manual Enable/Disable/Self-test

The Power Button on the front of the UPS is used to manually enable or disable the output of the 1609-B UPS.
The UPS supports a USB communication port for the end user to connect with a computer. The
user may monitor all the UPS status through the USB port if the 1609 UPS Management
Software is installed in the computer. The software is stored in the CD and can be found in the
accessory bag.
Selected 'DISABLE' for Manual Enable/Disable the UPS's Output.
Selected 'ENABLE' for Remote Enable/Disable the UPS's Output.
ENABLE
To enable the 1609-B UPS, press and hold the Power Button until one beep is
heard.
To disable the 1609-B UPS, press and hold the Power Button until three beeps
are heard then release immediately (takes approximately 3 seconds).
To perform a self-test, press and hold the Power Button until two beeps are
heard then release immediately.
Publication 1609-IN013B-EN-P - August 2012
1 and 2 On Battery Contact (NO)
3 and 4 Low Battery Contact (NO)
5 and 6 Fault
(Indicates UPS has faulted see the User Manual trouble
shooting section)
7 and 8 Remote Enable/Disable
(Closed for Output Enable, Open for Output Disable)