Lifetime Expectancy And Mean Time Between Failure - Allen-Bradley 1606-XLS240-UPSC Reference Manual

Dc-ups with integrated battery - 24v, 10 a
Table of Contents

Advertisement

DC-UPS with Integrated Battery - 24V, 10 A
Lifetime Expectancy and
Mean Time between
Failure
Attribute
Lifetime
expectancy
MTBF
(1) The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the
built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitors manufacturer specification. The
prediction model allows a calculation of up to 15 years (131,400 h) from date of shipment.
(2) MTBF represents Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical
representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
All values except a battery.
18
(1)
(2)
SN 29500, IEC 61709
MIL HDBK 217 F
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
Description
min. 137,400 h
at 10 A output current and 40 °C (104 °F)
min. > 15 years
at 5 A output current and 40 °C (104 °F)
min. > 15 years
at 10 A output current and 25 °C (77 °F)
886,000 h
at 10 A output current and 40 °C (104 °F)
1,482,000 h
at 10 A output current and 25 °C (77 °F)
397,900 h
at 10 A output current and 40 °C (104 °F), Ground Benign GB40
545,000 h
at 10 A output current and 25 °C (77 °F), Ground Benign GB25