Approximate Dimensions And Weight; Installation Notes - Allen-Bradley 1606-XLS240-UPSC Reference Manual

Dc-ups with integrated battery - 24v, 10 a
Table of Contents

Advertisement

Approximate Dimensions
and Weight
Figure 24 - Front View

Installation Notes

Attribute
Description
Width
123 mm (4.84 in.)
Height
124 mm (4.88 in.)
(1)
Depth
119 mm (4.69 in.)
Weight
2850 g (6.28 lb)
DIN Rail
Use 35 mm heavy duty DIN rails according to EN 60715 or EN 50022.
(1) The DIN rail height must be added to the unit depth of 119 mm (4.68 in.) to calculate the total required installation depth.
Dimensions are inches and millimeters.
The unit shall only be installed and put into operation by qualified personnel.
ATTENTION: This unit is designed for installation in an enclosure and is
intended for general use, such as in industrial control, office, communication,
and instrumentation equipment. Do not use this device in aircraft, trains and
nuclear equipment, where malfunctioning of the power supply may cause
severe personal injury or threaten human life.
ATTENTION: Risk of electrical shock, fire, personal injury, or death.
– Turn power off before working on the device. Protect against inadvertent
re powering.
Do not modify or repair the unit.
Do not open the unit as high voltages are present inside.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be
expected.
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
DC-UPS with Integrated battery - 24V, 10 A
Figure 25 - Side View
23

Hide quick links:

Advertisement

Table of Contents