Output In Buffer Mode - Allen-Bradley 1606-XLS240-UPSC Reference Manual

Dc-ups with integrated battery - 24v, 10 a
Table of Contents

Advertisement

DC-UPS with Integrated Battery - 24V, 10 A
Figure 6 - Input to Output Voltage Drop, Typ.

Output in Buffer Mode

8
If the input voltage falls below a certain value (transfer threshold level), the
DC-UPS starts buffering without any interruption or voltage dips. Buffering is
possible even if the battery is not fully charged.
Attribute
Description
Output voltage
Nom
Transfer threshold for
Typ
buffering
Ripple and noise
Max
voltage
Output current
Nom
Short Circuit current
Min
Max
(1) If the output current is in the range 10 A...15 A for longer than 5 s, a hardware-controlled reduction of the maximal output current
to 10 A occurs. If the 10 A are not sufficient to maintain the 24V, buffering stops after another 5 s. The buffering is possible again as
soon as the input voltage recovers.
(2) If the nominal output voltage cannot be maintained in buffer mode, the DC-UPS switches off after 5 s to save battery capacity.
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
Figure 7 - Output Voltage versus Output Current in Normal
Mode at 24V Input, Typ.
24V DC
The output voltage is stabilized and independent from the
battery voltage.
at no load
22.45V
at 10 A output current
22.25V
80 mV greater than the output voltage in buffer mode.
20 mVpp
20 Hz to 20 MHz, 50 Ohms
10 A
Continuously allowed
15 A
<5 s with full output voltage
17.9 A
Load impedance 100 mOhm
21 A
Load impedance 100 mOhm
(1)
(2)
(2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents