DC-UPS with Integrated Battery - 24V, 10 A
26
4. Remove the battery by pulling on the strap.
5. Install the new battery.
6. Connect the red cable (+) to the red positive (+) terminal on the battery.
7. Connect the black cable (-) to the black negative (-) terminal on the
battery.
8. Close the cover.
9. Tighten the captive cover screw.
10. Plug in the fuse.
Disposing of the Battery
At the end of its life, the battery that is contained in this product should be
collected separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and
Pb
contributes to the conservation of natural resources as valuable materials are
recovered.
Batteries that are marked with the recycling symbol should be recycled through a
competent agency.
Replacement Battery Specifications
The replacement battery needs to meet the requirements in the following table.
Attribute
Description
Battery type
Nom
12V, 4...6 Ah
Design life
Min
3...5 years
Dimensions
Nom
70 x 106 x 90 mm
(2.75 x 4.17 x 3.54 in.)
Pole connection
6.35 mm (0.25 in.)
Approvals
UL, Vds
Allowed discharge
Min
29 A
current
(1) Maximum case height of 102 mm (4.01 in.).
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
VRLA lead acid maintenance-free battery
Per EUROBAT guidelines
(1)
W x H x D
Blade type; fast-on
For applications that require UL or V ds