Environment - Allen-Bradley 1606-XLS240-UPSC Reference Manual

Dc-ups with integrated battery - 24v, 10 a
Table of Contents

Advertisement

DC-UPS with Integrated Battery - 24V, 10 A

Environment

Figure 22 - Nominal Mode - Output Current versus Ambient
Temperature
20
Attribute
Description
Operational temperature
0...40 °C (32...104 °F)
Storage temperature
-20...+50 °C (-4...+122 °F)
Relative humidity
5...95%
(1)
Vibration sinusoidal
2...17.8 Hz: ±1.6 mm (0.62 in.);
17.8...500 Hz: 1 g (0.03 oz)
Shock
15 g (0.52 oz) 6 ms,
10 g (0.35 oz) 11 ms
Altitude
0...6000 m (0...20,000 ft.)
Overvoltage category
III
II
Degree of pollution
2
(1) Use wall mounting accessory for greater values.
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
Full output power
Storage and transportation
IEC 60068-2-30
Do not energize while condensation is present.
IEC 60068-2-6
IEC 60068-2-27
Approvals apply up to 2000 m (6560 ft).
EN 50178
EN 50178, altitudes above 2000 (6560 ft)
EN 50178, non-conductive
Figure 23 - Buffer Mode - Output Current versus Ambient
Temperature

Hide quick links: