Terminals and Wiring

Attribute
Type
Solid wire
Stranded wire
American Wire Gauge
Ferrules
Pull-out force
Tightening torque
Wiring stripping length
Figure 21 - Connecting a Wire with Spring-clamp Terminals
• Use appropriate copper cables that are designed for an operating
temperature of 60 °C (140 °F)
• Follow national installation codes and regulations.
• Ensure that all strands of a stranded wire enter the terminal connection.
• You can use up to two stranded wires with the same cross section in one
connection point.
Rockwell Automation Publication 1606-RM003A-EN-P - March 2019
DC-UPS with Integrated battery - 24V, 10 A
Power Terminals
Bi-stable, quick-connect
spring- clamp terminals. IP20
Finger-touch-proof. Suitable for
field and factory installation.
Shipped in open position.
2
0.5...6 mm
2
0.5...4 mm
AWG 20...10
Allowed but not required
10 AWG:80 N, 12 AWG:60 N
14 AWG:50 N, 16 AWG:40 N
according to UL486E
Not applicable
10 mm (0.4 in.)
Signal Terminals
Plug connector with screw terminal.
Finger-touch-proof construction
with captive screws for 3.5 mm
slotted screwdriver. Suitable for field
and factory installation. Shipped in
open position. To meet GL
requirements, unused terminal
compartments should be closed.
2
0.2...1.5 mm
2
0.2...1.5 mm
AWG 22...14
Allowed but not required
Not applicable
1 Nm, 9 lb-in
6 mm (0.24 in.)
17