Electro-mechanical starter screen

Figure 34: Electro-mechanical starter screen
This screen displays all information pertaining to the Electro-Mechanical Starter.
Table 91: Display only
Field/LED name
Motor Run (LED)
Motor Current % Full Load
Amps
Current Limit Setpoint
Pulldown Demand Time Left
98
Description
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Displays the motor current as a percentage of the Full Load Amps
(FLA) value. For the Electro-Mechanical Starter this is the data
returned by the CM-2 board.
Displays the current limit value in use. This value could come from
a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog
Remote mode, PWM signal in Digital Remote mode, E-Link Gateway
interface in ISN mode, or a locally programmed value.
Displays the time remaining in the programmed pulldown period if
the value is nonzero.