Medium voltage Solid State Starter screen

Figure 37: Medium voltage Solid State Starter screen
This screen displays all information pertinent to the Medium Voltage Solid State Starter (MVSSS).
Table 100: Display only
Field/LED name
Motor Run (LED)
Motor Heater (LED)
Motor Current % Full Load
Amps
Current Limit Setpoint
Input Power
KW Hours
Starter Model
Voltage – Phase A, B, C
Current – Phase A, B, C
104
Description
Indicates when the OptiView Control Center is commanding the
motor to run.
Indicates whether the optional Motor Heater is ON or OFF.
Displays the motor current as a percentage of Job Full Load Amps
Setpoint.
Displays the current limit in use. This value could come from a
0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog
Remote mode, PWM signal in Digital Remote mode, E-Link or SC-
EQ communications interface in ISN Remote mode or a locally
programmed value in Local mode.
Displays the kilowatts measured by and transmitted from the
starter.
Displays the cumulative kilowatt hours. The microboard calculates
this value from the Input Power transmitted from the starter. When
the number exceeds 999999 KWH, the value will rollover to zero.
Displays the starter model number as transmitted from the starter.
Displays the 3-phase input line voltage as measured by and
transmitted from the starter.
Displays the 3-phase motor current as measured by and transmitted
from the starter.
YK-EP Style B Centrifugal Chiller