York YK-EP Operation And Maintenance Manual page 68

Centrifugal chiller
Hide thumbs Also See for YK-EP:
Table of Contents

Advertisement

Table 54: Programmable
Button
Access level
High Limit
Low Limit
VGD Count
Admin
Extreme Stall
Duration
PRV VGD
Inhibit
Table 55: Navigation
Button
Access Level Description
Home
Service
VGD Screen
Service
68
Description
0.5 to 1.2VDC; default 0.6VDC
Specifies the Stall Detector Board output voltage that represents an
acceptable amount of stall noise.
The minimum difference between the High Limit Setpoint and the
Low Limit Setpoint is 0.1VDC. If a Low Limit Setpoint is entered
which is less than 0.1VDC below the High Limit Setpoint, the High
Limit Setpoint is adjusted so that it is 0.1VDC above the newly
entered Low Limit value.
0.3 to 0.8VDC; default 0.5VDC
In the Stall Reacting State, the VGD is driven closed until the Stall
Detector Board output voltage decreases to this level.
The minimum difference between the High Limit Setpoint and the
Low Limit Setpoint is 0.1VDC. If a Low Limit Setpoint is entered
which is less than 0.1VDC below the High Limit Setpoint, the High
Limit Setpoint is adjusted so that it is 0.1VDC above the newly
entered Low Limit value.
Allows the user to clear the VGD Cycle Count.
10 to 20 minutes; default 10
Specifies the maximum allowed time an extreme stall condition can
exist before the VGD operation is disabled and driven to the full
open position to protect it from damage.
40% - 100% default 100%
While the Pre-Rotation Vanes position is greater than this setpoint,
extreme stall conditions are not checked, the VGD control is
inhibited and the VGD is pulsed open according to the Open Pulse
Setpoint. While this is in effect, PRV Position Override is displayed as
Control Status.
Returns user to HOME Screen.
Returns user to VARIABLE GEOMETRY DIFFUSER Screen
YK-EP Style B Centrifugal Chiller