Harmonic filter details screen

Figure 45: Harmonic filter details screen
This screen displays more detailed information pertaining to the IEEE-519 Harmonic Filter.
Table 124: Display only
Field/LED
Access level
name
Motor Run
(LED)
Motor
Current %
Full Load
Amps
Current Limit
Setpoint
Pulldown
Demand
Time Left
Operating
Mode (Run /
Stop)
VSD Model
Service
YK-EP Style B Centrifugal Chiller
Description
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Displays the motor current as a percentage of the Full Load Amps
(FLA) value. For the Variable Speed Drive this is the data returned by
the VSD Logic Board.
Displays the current limit value in use. This value could come from
a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog
Remote mode, PWM signal in Digital Remote mode, E-Link or SC-
EQ communications interface in ISN mode, or a locally programmed
value.
Displays the time remaining in the programmed pulldown period if
the value is nonzero.
Indicates whether the Harmonic Filter is operating.
Displays the horsepower for which the attached Harmonic Filter is
configured.