York YK-EP Operation And Maintenance Manual page 219

Centrifugal chiller
Hide thumbs Also See for YK-EP:
Table of Contents

Advertisement

the total RMS value of all the harmonic current supplied by the main power to the VSD divided by
the chiller Full Load Amps, in percent. A standard VSD, less the optional filter typically has an input
current TDD level on the order of 28-30%. The chiller can be started after the Operator presses the
WARNING RESET button.
VSD – Low Frequency Detected
After a 20 second bypass after entering System Run, if the VSD frequency decreases to below 1 Hz
less than the minimum allowed frequency for 25 continuous seconds, this shutdown is initiated.
The minimum allowed frequency for the VSD is 25 Hz for 50 Hz units; 30 Hz for 60 Hz units. The
Operator must press the WARNING RESET button to reset the fault.
YK-EP Style B Centrifugal Chiller
219