York YK-EP Operation And Maintenance Manual page 141

Centrifugal chiller
Hide thumbs Also See for YK-EP:
Table of Contents

Advertisement

Table 137: Display only
Button
Leaving Chilled Liquid
Temperature Cycling –
Restart
Current Limit Setpoint
Table 138: Programmable
Button
Access level
Pulldown
Demand
Operator
Limit
Pulldown
Demand
Operator
Time
Print
View
Local Motor
Operator
Current Limit
Local Leaving
Chilled Liquid
Operator
Temperature
– Range
YK-EP Style B Centrifugal Chiller
Description
Displays the Leaving Chilled Liquid Temperature at which the chiller
will restart after it has shut down due to over-cooling temperature.
This value is calculated by adding the Leaving Chilled Liquid
Temperature Cycling Offset – Restart to the Leaving Chilled Liquid
Temperature – Setpoint.
Displays the active Current Limit Setpoint.
In Local mode, this is the locally programmed Current Limit
Setpoint. In ISN Remote mode, this is the setpoint received from the
E-Link or SC-EQ communications interface. In Analog Remote mode,
this is the setpoint received via 0 to 10VDC, 2 to 10VDC, 0 to 20mA
or 4 to 20mA input. In Digital Remote mode, this is the Pulse width
Modulation signal input.
Description
Allows the user to specify the current limit value (as a percentage
of Full Load Amps) to which the chiller will be limited during the
specified pulldown limit time. Adjustable from 30% to 100%, Default
= 100%. This value will override the Motor Current Limit value during
this time period. This function is used to provide energy savings
following chiller start-up.
Allows the user to set a period of time for which the pulldown
demand limit will be in effect after the chiller starts.
Generates setpoints print report.
Allows the user to specify the maximum allowed motor current (as
a percentage of FLA). Adjustable from 30% to 100%, Default = 100%.
When the motor current reaches this value, the Pre-Rotation Vanes
will not be permitted to open further. If the motor current rises
above this value, the Pre-Rotation Vanes will close to reduce the
current to this value.
This is the range over which an analog signal (0 to 20 mA, 4 to 20mA,
0 to 10VDC or 2 to 10VDC) in Analog Remote mode or a digital
signal (PWM) in Digital Remote mode can reset the Leaving Chilled
Liquid Temperature Setpoint above the operator programmed BASE
Setpoint.
Programmable from 10°F to 40°F, with a default of 10°F, it is added
to the BASE value to create a range over which the remote device
can reset the setpoint. For example, if this setpoint is programmed
for 10°F and the operator programmed value is 45°F, then the
remote device can set the Leaving Chilled Liquid Temperature
Setpoint over the range of 45.0°F to 55.0°F.
141