Mod "A" Solid State Starter Screen - York YK-EP Operation And Maintenance Manual

Centrifugal chiller
Hide thumbs Also See for YK-EP:
Table of Contents

Advertisement

Mod "A" Solid State Starter screen

Figure 35: Mod "A" Solid State Starter screen
This screen displays all information pertaining to the Mod "A" Solid State Starter.
Table 94: Display only
Field/LED name
Motor Run (LED)
Motor Heater (LED)
Motor Current % Full Load
Amps
Current Limit Setpoint
Pulldown Demand Time Left
Scale/Model
Voltage – Phase A, B, C
Current – Phase A, B, C
100
Description
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Indicates whether the optional Motor Heater is ON or OFF.
Displays the motor current as a percentage of the Full Load Amps
(FLA) value. This is the data returned by the Starter Logic Board for
the Solid State Starter.
Displays the current limit value in use. This value could come from
a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog
Remote mode, PWM signal in Digital Remote mode, E-Link Gateway
interface in ISN mode, or a locally programmed value.
Displays the time remaining in the programmed pulldown period if
the value is nonzero.
Display information about the Liquid Cooled Solid State Starter
Rating and the maximum allowed Full Load Amps.
Display the 3-phase input line voltage values being read from the
Solid State Starter.
Display the 3-phase motor current values being read from the Solid
State Starter.
YK-EP Style B Centrifugal Chiller