Table 107: Motor rated voltage (V)*
Model in HP
900
1000
1250
1500
1750
2000
2250
2500
Note: *Max. Job/Rated 100% FLA (A) (Programmed Drive Current)
Table 108: Programmable
Button
Access level
Local Motor
Operator
Current Limit
Pulldown
Demand
Operator
Limit
Pulldown
Demand
Operator
Time
Full Load
Service
Amps
KWH Reset
Service
Table 109: Navigation
Button
Access level
Home
View
ACC Details
Service
Motor Lube
Motor Details Service
110
2300 V
202 A
224 A
280 A
336 A
392 A
438 A
494 A
561 A
Description
Allows the user to specify the maximum allowed motor current (as
a percentage of FLA). When the motor current reaches this value,
the Pre-Rotation Vanes will not be permitted to open further. If the
motor current rises above this value, the Pre-Rotation Vanes will
close to reduce the current to this value.
Allows the user to specify the current limit value (as percentage
of FLA) to which the chiller will be limited during the specified
pulldown limit time. This value will override the Motor Current
Limit value during this time period. This function is used to provide
energy savings following chiller start-up.
Allows the user to set a period of time for which the pulldown
demand limit will be in effect after the chiller starts.
Defines the maximum amps at which the motor can operate this
value is viewable when logged in at VIEW or OPERATOR level.
The maximum programmable value of this setpoint is equal to
Programmed Drive Current value received from the MVVSD.
Allows the user to reset the cumulative Kilowatt hours to zero.
Description
Returns user to HOME Screen.
Moves to a subscreen which provides more information about the
Adaptive Capacity Control.
Moves to a subscreen allowing operator acknowledgement of the
compressor motor lubrication and viewing of the compressor motor
lubrication parameters.
Moves to a subscreen that provides information and setpoints
pertinent to the Motor Monitoring feature.
3300 V
141 A
156 A
195 A
235 A
274 A
312 A
345 A
391 A
YK-EP Style B Centrifugal Chiller
4160 V
112 A
125 A
155 A
186 A
217 A
248 A
274 A
310 A