Table 85: Condenser refrigerant level
Actual level
0% to 15%
16% to 31%
32% to 47%
48% to 63%
64% to 79%
79%
Table 86: Programmable
Button
Access level
Level
Service
Setpoint
Startup
Service
Position
Startup Delay Admin
Ramp Time
Admin
High
Service
Threshold
Low
Service
Threshold
Kp
Admin
Ti
Admin
Td
Admin
Manual
Service
Increment
Open
94
Control valve
command %
50%
60%
70%
80%
90%
100%
Description
Displays the Condenser Level Control Setpoint for the PID control.
The value will display in tenths. (Adjustable form 20 to 80%; default
50%).
Displays the Startup Position programming button. This button will
also contain a text box displaying the Condenser Level Control Valve
Startup Position. The value will display in tenths. (Adjustable 0 to
100%; default 50%).
The amount of time the refrigerant level valve PID waits after start
before it starts controlling the valve position. This allows the system
to stabilize before making valve position changes. (Can be adjusted
at 15 seconds).
After the chiller has been running for the level control startup delay
time, if the refrigerant level is less than the Level Setpoint, a linearly
increasing ramp is applied to the Level Setpoint. This ramp allows
the level to go from the present level to the programmed Level
Setpoint over a period of time programmed as the Ramp Up Time.
(1 to 5 minutes; default 1 min).
Sets the high limit for the Subcooler Effectiveness Warning
(Adjustable 0 to 100%; default 50%).
Sets the low limit for the Subcooler Effectiveness Warning
(Adjustable 0 to 100%; default 50%).
Sets the Proportional value of the PID control loop. (Adjustable 0.1
to 15; default 0.5).
Sets the Integral value of the PID control loop. (Adjustable 0.1 to
500; default 200).
Sets the Derivative value of the PID control loop. (Adjustable 0.0 to
200; default 0.0).
This sets the percentage the refrigerant valve will manually be
driven with each press of the Open or Close buttons. (0.1 to 10%;
default 1.0%).
Pressing this button will set the Condenser Level Control Valve
Mode to Manual, if it had been in Auto and will increase the current
Condenser Level Control Valve Command by an amount equal to the
Manual Increment, with a maximum of 100.0%.
YK-EP Style B Centrifugal Chiller