Variable Speed Drive (VSD) details screen (VSD with part
number 371-02767-XXX (60 Hz) or 371-03700-XXX (50 Hz))
Figure 41: Variable Speed Drive (VSD) details screen (VSD with part number 371-02767-XXX (60
Hz) or 371-03700-XXX (50 Hz))
This screen displays more detailed information pertaining to a Variable Speed Drive (VSD).
Note: Requires a login access level of SERVICE.
Table 113: Display only
Field/LED
Access level
name
Motor Run
(LED)
Motor
Current %
Full Load
Amps
Current Limit
Setpoint
Pulldown
Demand
Time Left
Water Pump
Output (LED)
114
Description
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Displays the motor current as a percentage of the Full Load Amps
(FLA) value. For the Variable Speed Drive this is the data returned by
the VSD Logic Board.
Displays the current limit value in use. This value could come from
a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog
Remote mode, PWM signal in Digital Remote mode, E-Link or SC-
EQ communications interface in ISN mode, or a locally programmed
value.
Displays the time remaining in the programmed pulldown period if
the value is nonzero.
Indicates whether the relay controlling the water pump output is
energized.