Type Of Connection To The Mains - eka MILLENIAL MKF 464 TS Installation And Maintenance Manual

Electronic ovens with touch screen
Table of Contents

Advertisement

3.9 Type of connection to the mains

400V 3PH + N ~
Connect the 3 phase conductors (L1, L2, L3) of the cable respectively to the terminals of the terminal board
marked with "1"(brown conductor), "2"(black conductor) and "3"(grey conductor) and the neutral (N)
conductor to the terminals marked with "4" or "5" (blue conductor); the earth conductor (yellow/green)
must be connected to the terminal marked with the symbol
board).
230V 3PH ~
Connect the 3 phase conductors (L1, L2, L3) of the cable respectively to the terminals of the terminal board
marked with "1" and "2" (brown conductor), with "3" and "4" (black conductor) and with "5" (grey
conductor); the earth conductor (yellow/green) must be connected to the terminal marked with the
symbol
(see diagram available near the terminal board).
230V ~
Connect the conductor of phase (L) of the cable to the terminals of the terminal board marked with "1",
"2" and "3" (brown conductor) and the neutral (N) conductor to the terminals marked with "4" and "5"
(blue conductor); the earth conductor (yellow/green) must be connected to the terminal marked with the
symbol
(see diagram available near the terminal board).
mod. MKF 464 TS – MKF 511 TS
mod. MKF 664 TS – MKF 711 TS
mod. MKF 711 V TS
mod. MKF 611 C TS
(see diagram available near the terminal
6