Installation

9.1.2 System isolator

9.1.3 Point of injection, Bello Zon
22
WARNING!
Warning against unchecked through-suction
If the line that is carrying the water to be treated is subject to
a vacuum pressure, then unchecked through-suction of the
ClO
solution can occur.
2
Fit a system isolator.
Fit a backpressure-free back pressure valve upstream of
the injection point, if a constant back pressure of 1.5 bar
is not ensured in any other way.
®
CDL
WARNING!
Danger of back pressure effects
If incorrectly installed, the integrated non-return valve may
not close.
Install the ClO
points vertically downwards
WARNING!
Warning of toxic ClO
If the metering line is made from inappropriate material, e.g.
PE, it may leak.
Always use PTFE tube, e.g. 6x4 mm, order no. 37426 or
equivalent.
WARNING!
Warning of too-low ClO
UV radiation, e.g. from fluorescent strip lights or sunshine, or
bright light can cause the ClO
pose.
Protect the metering line against UV radiation and bright
light.
P_PMA_BEZ_0078_SW
connector of the point of injection so it
2
2
concentration
2
in the metering line to decom‐
2