5.2 Shutting Down and Powering Off the UPS

Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
After the inverter shuts down, the UPS works in bypass mode if the bypass is normal, as
shown in
abnormal, as shown in
Issue 02 (2020-01-10)
On the LCD
On the main screen, tap Common Functions. Tap Inv. OFF.
To shut down the inverter on the Maintenance screen, tap System Info > Maintenance.
On the WebUI
On the homepage, choose Monitoring > Control, and click Inv. OFF. In the displayed
dialog box, click OK to shut down the inverter.
Figure
5-11; the UPS supplies no power and the loads power off if the bypass is
Figure
Copyright © Huawei Technologies Co., Ltd.
5-11.