UPS5000-A-500 kVA
User Manual (e-shelter)
After you restart the device, IP address allocation changes back to Manual. The IP address is set to the
IP address set previously.
Item
IP address
Subnet mask
Gateway
NAT mapping
RS485
address/RS485
baud rate
Figure 4-14 Communication screen 2
Item
RS485
Parity
mode
Issue 02 (2020-01-10)
Description
Set an Ethernet IP address that ranges from 1.0.0.0 to
223.255.255.255. The default value is 192.168.0.10.
NOTICE
Ensure that the UPS IP address is unique on the network segment. Otherwise,
the WebUI display function may not function properly.
Set an Ethernet subnet mask that ranges from 0.0.0.0 to
255.255.255.255. The default value is 255.255.255.0.
Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255.
The default value is 192.168.0.1.
NAT means network address translation. If it is set to Disable,
Internet cannot access IP addresses in the local area network (LAN).
The default value is Disable.
Set an address that ranges from 1 to 254 for this port. RS485 baud
rate depends on the network management conditions.
The default values of RS485 address and RS485 baud rate are 1 and
9600 respectively.
Description
Verify the validity of RS485 communication characters. When a device
node adopts RS485 communication, ensure that the parity modes for the
device nodes are set to the same mode. Available parity modes include
None, Odd, and Even.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
86