Huawei UPS5000-A-500 kVA User Manual page 137

Table of Contents

Advertisement

UPS5000-A-500 kVA
User Manual (e-shelter)
Table 4-15 RCCMD TRAP signal
Signal Name
#MODEL
#OUTPOWER
#OUTVOLT
#OUTCURR
#OUTLOAD
#BATTCAP
#INVOLT
#BYPASSINVOLT
#TEMPDEG
#AUTONOMTIME
#STATUS
#RUNTIME
#BATTVOLT
#INFREQ
#BYPASSINFREQ
#OUTFREQ
#CNT_PF
#CNT_BL
#INPHASES
#OUTPHASES
When you add a job, five sending methods are available. The latter three methods can take
effect only when the event condition is still true after the specified seconds.
Issue 02 (2020-01-10)
Immediately, once: After the event happens, the job will be sent to the RCCMD client
immediately.
Scheduled in X seconds: After the event happens, the job will be sent to the RCCMD
client once in X seconds. No matter whether the event disappears or not within X
seconds, the job will be sent.
After X seconds, repeat all Y Specify the interval: After the event happens, the job will
be sent once in X seconds, and then be sent once every Y seconds.
After X seconds on Battery: After the battery mode is activated for X seconds, the job
will be sent to the RCCMD client once.
At X seconds remaining time: When the battery backup time has only X seconds left,
the job will be sent to the RCCMD client once.
Copyright © Huawei Technologies Co., Ltd.
Description
Device name
Active power
Output voltage
Output current
Output load rate
Remaining battery capacity
Input voltage
Bypass input voltage
Temperature inside the UPS
Battery backup time
UPS status
UPS operating time
Battery voltage
Input frequency
Bypass input frequency
Output frequency
Power supply failure times
Low battery voltage times
Input phases
Output phases
4 User Interface
Unit in the UPS
N/A
kW
V
A
%
%
V
V
Celsius
minutes
N/A
minutes
V
Hz
Hz
Hz
N/A
N/A
N/A
N/A
129